Function Block; Signals; Settings - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 135-UEN A
9.3.3
9.3.4
9.3.5
Table 144:
ROV2PTOV Group settings (basic)
Name
Values (Range)
Operation
OperationStep1
Characterist1
Table continues on next page
Technical manual
ROV2PTOV has two voltage steps, where step 1 can be set as inverse or definite time
delayed. Step 2 is always definite time delayed.

Function block

ROV2PTOV
U3P*
TRIP
BLOCK
TR1
BLKST1
TR2
BLKST2
START
ST1
ST2
IEC09000273_1_en.vsd
IEC09000273 V1 EN
Figure 96:
ROV2PTOV function block

Signals

Table 142:
ROV2PTOV Input signals
Name
U3P
BLOCK
BLKST1
BLKST2
Table 143:
ROV2PTOV Output signals
Name
TRIP
TR1
TR2
START
ST1
ST2

Settings

Unit
Off
-
On
Off
-
On
Definite time
-
Inverse curve A
Inverse curve B
Inverse curve C
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
General trip signal
BOOLEAN
Trip signal from step 1
BOOLEAN
Trip signal from step 2
BOOLEAN
General start signal
BOOLEAN
Start signal from step 1
BOOLEAN
Start signal from step 2
Step
Default
-
Off
-
On
-
Definite time
Section 9
Voltage protection
Description
Operation Off / On
Enable execution of step 1
Selection of time delay curve type for step
1
217