Introduction

The 1Ph High impedance differential protection HZPDIF functions can be used when
the involved CT cores have the same turns ratio and similar magnetizing
characteristics. Each utilizes an external summation of the currents in the
interconnected CTs, a series resistor, and a voltage dependent resistor which are
mounted externally connected to the IED.
The external resistor unit shall be ordered under accessories.
HZPDIF can be used as high impedance REF protection.

Function block

HZPDIF
ISI*
TRIP
BLOCK
ALARM
BLKTR
MEASVOLT
IEC05000363-2-en.vsd
IEC05000363 V2 EN
Figure 48:
HZPDIF function block

Signals

Table 44:
HZPDIF Input signals
Name
Type
ISI
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
Table 45:
HZPDIF Output signals
Name
Type
TRIP
BOOLEAN
ALARM
BOOLEAN
MEASVOLT
REAL
Default
Description
-
Group signal for current input
0
Block of function
0
Block of trip
Description
Trip signal
Alarm signal
Measured RMS voltage on CT secondary side
1MRK 504 135-UEN A
Technical manual