Line differential protection RED650 2.2 IEC
Technical manual

Test mode functionality TESTMODE

Functionality

When entering IED test mode there is an option to block all functions. Active test
mode is indicated by a flashing yellow Start LED on the LHMI. After that, it is
possible to unblock arbitrarily selected functions from the LHMI to perform
required tests.
When leaving TESTMODE, all blockings are removed (except for functions that
have their block input active), and the IED resumes normal operation. However, if
during TESTMODE operation, power is removed and later restored, the IED will
remain in TESTMODE with the same protection functions blocked or unblocked as
before the power was removed. All testing will be done with actually set and
configured values within the IED. No settings will be changed, thus mistakes are
avoided.
Forcing of binary input and output signals is only possible when the IED is in IED
test mode.

Function block

TESTMODE
IED_TEST
TEST
IED_TEST
BLOCK
NOEVENT
INPUT
SETTING
IEC61850
IEC14000072-1-en.vsd
IEC09000219 V2 EN-US
Figure 366:
TESTMODE function block

Signals

Table 590:
TESTMODE Input signals
Name
Type
IED_TEST
BOOLEAN
Table 591:
TESTMODE Output signals
Name
Type
TEST
BOOLEAN
IED_TEST
BOOLEAN
BLOCK
BOOLEAN
Table continues on next page
Basic IED functions
Default
Description
0
Activate IED test mode
Description
In test via IED TEST or via LD0 Mode
IED test mode is active
Active when LD0 is blocked or test blocked
Section 21
IP1647-1 v3
M4803-3 v10
SEMOD54888-4 v5
IP9680-1 v2
PID-6730-INPUTSIGNALS v1
PID-6730-OUTPUTSIGNALS v1
791