1MRK 504 135-UEN A
8.8.2.4
Table 112:
GOPPDOP Group settings (basic)
Name
Values (Range)
Operation
OpMode1
Power1
Angle1
TripDelay1
OpMode2
Power2
Angle2
TripDelay2
Table 113:
GOPPDOP Group settings (advanced)
Name
Values (Range)
k
Table 114:
GOPPDOP Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
Mode
Technical manual
Name
START1
START2
P
PPERCENT
Q
QPERCENT

Settings

Unit
Off
-
On
Off
-
OverPower
0.0 - 500.0
%
-180.0 - 180.0
Deg
0.010 - 6000.000
s
Off
-
OverPower
0.0 - 500.0
%
-180.0 - 180.0
Deg
0.010 - 6000.000
s
Unit
0.00 - 0.99
-
Unit
1 - 6
-
L1, L2, L3
-
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
Type
Description
BOOLEAN
Start signal from stage 1
BOOLEAN
Start signal from stage 2
REAL
Active Power
REAL
Active power in % of calculated power base value
REAL
Reactive power
REAL
Reactive power in % of calculated power base
value
Step
Default
-
Off
-
OverPower
0.1
1.0
0.1
0.0
0.001
1.000
-
OverPower
0.1
1.0
0.1
0.0
0.001
1.000
Step
Default
0.01
0.00
Step
Default
1
1
-
Pos Seq
Section 8
Current protection
Description
Operation Off / On
Operation mode 1
Power setting for stage 1 in % of
calculated power base value
Characteristic angle for stage 1
Trip delay for stage 1
Operation mode 2
Power setting for stage 2 in % of
calculated power base value
Characteristic angle for stage 2
Trip delay for stage 2
Description
Low pass filter coefficient for power
measurement, U and I
Description
Selection of one of the Global Base Value
groups
Mode of measurement for current and
voltage
191