OC4PTOC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
MeasType
8.2.6
8.2.7
Technical manual
Unit
1 - 6
-
DFT
-
RMS
Monitored data
Table 77:
OC4PTOC Monitored data
Name
DIRL1
DIRL2
DIRL3
IL1
IL2
IL3
Operation principle
The Four step phase overcurrent protection 3-phase output OC4PTOC is divided into
four different sub-functions, one for each step. For each step x , where x is step 1, 2,
3 and 4, an operation mode is set by DirModex: Off/Non-directional/Forward/
Reverse.
The protection design can be divided in four parts:
•
The direction element
•
The harmonic Restraint Blocking function
•
The four step over current function
•
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModex shall be left to default value, Non-directional.
Step
Default
1
1
-
DFT
Type
Values (Range)
INTEGER
1=Forward
2=Reverse
0=No direction
INTEGER
1=Forward
2=Reverse
0=No direction
INTEGER
1=Forward
2=Reverse
0=No direction
REAL
-
REAL
-
REAL
-
Section 8
Current protection
Description
Selection of one of the Global Base Value
groups
Selection between DFT and RMS
measurement
Unit
Description
-
Direction for phase L1
-
Direction for phase L2
-
Direction for phase L3
A
Current in phase L1
A
Current in phase L2
A
Current in phase L3
147