1MRK 504 135-UEN A
Section 2
2.1
IEC 61850 or
ANSI
Function name
Differential protection
T2WPDIF
87T
T3WPDIF
87T
REFPDIF
87N
HZPDIF
87
Impedance protection
ZMRPSB
68
ZGCPDIS
21G
LEPDIS
2.2
IEC 61850 or
ANSI
Function name
Current protection
PHPIOC
50
OC4PTOC
51/67
EFPIOC
50N
EF4PTOC
51N/67N
TRPTTR
49
Table continues on next page
Technical manual
Available functions
Main protection functions
Function description
Transformer differential protection, two winding
Transformer differential protection, three winding
Restricted earth fault protection, low impedance
1Ph High impedance differential protection
Power swing detection
Underimpedance protection for generators and
transformers
Load encroachment
Back-up protection functions
Function description
Instantaneous phase overcurrent protection, 3–
phase output
Four step phase overcurrent protection, 3-phase
output
Instantaneous residual overcurrent protection
Four step residual overcurrent protection, zero/
negative sequence direction
Thermal overload protection, two time constants
Available functions
Transformer
0–1
1
0–1
0–3
2
0–2
2
0–1
0–1
0–1
Transformer
0–3
2
3
0–3
2
3
0–3
2
3
0–3
2
3
0–3
2
3
Section 2
1
3
2
2
2
2
35