Technical Data; Trip Matrix Logic Tmaggio; Identification; Functionality - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 135-UEN A
13.1.7
13.2
13.2.1
13.2.2
Technical manual
BLOCK
TRIN
Operation Mode = On
Program = 3Ph
IEC05000789 V1 EN
Figure 164:
Simplified logic diagram for three phase trip
Lockout can be activated either by activating the input (SETLKOUT) or
automatically from trip input by setting AutoLock to On. A Lockout condition will be
indicated by activation of the output (CLLKOUT). If lockout has been activated it can
be reset by activating the input (RSTLKOUT) or via the HMI.
If TripLockout is set to On an active Lockout will result in a three-phase trip output.
In this way if both AutoLock and TripLockout are set to On the trip will always be
three-phase and sealed in.

Technical data

Table 278:
SMPPTRC technical data
Function
Trip action
Timers

Trip matrix logic TMAGGIO

Identification

Function description
Trip matrix logic

Functionality

The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route
trip signals and other logical output signals to the tripping logics SMPPTRC and
SPTPTRC or to different output contacts on the IED.
tTripMin
AND
t
Range or value
3-ph
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
TMAGGIO
-
Section 13
Logic
TRIP
OR
en05000789.vsd
Accuracy
-
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
373