Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number
of operations has reached a predefined value. The energy is calculated from the
measured input currents as a sum of I
calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
•
breaker open and close travel time
•
spring charging time
•
number of breaker operations
•
Y
accumulated I
t per phase with alarm and lockout
•
remaining breaker life per phase
•
breaker inactivity
Function block
GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
Figure 215:
SSCBR function block
Signals
Table 410:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ALMPRES
BOOLEAN
Table continues on next page
y
t values. Alarms are generated when the
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Block all the alarms
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Binary pressure alarm input