Functionality; Function Block; Signals - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 14
Monitoring
14.17.2
14.17.3
14.17.4
498

Functionality

The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number
of operations has reached a predefined value. The energy is calculated from the
measured input currents as a sum of I
calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
breaker open and close travel time
spring charging time
number of breaker operations
Y
accumulated I
t per phase with alarm and lockout
remaining breaker life per phase
breaker inactivity

Function block

GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
Figure 215:
SSCBR function block

Signals

Table 410:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ALMPRES
BOOLEAN
Table continues on next page
y
t values. Alarms are generated when the
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Block all the alarms
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Binary pressure alarm input