Function block

DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
IEC09000134 V1 EN
Figure 265:
DOSLAN1 function block

Signals

Table 513:
DOSLAN1 Output signals
Name
Type
LINKUP
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN

Settings

The function does not have any parameters available in the local HMI or PCM600.

Monitored data

Table 514:
DOSLAN1 Monitored data
Name
Type
State
INTEGER
Quota
INTEGER
IPPackRecNorm
INTEGER
IPPackRecPoll
INTEGER
IPPackDisc
INTEGER
NonIPPackRecNorm
INTEGER
NonIPPackRecPoll
INTEGER
NonIPPackDisc
INTEGER
Basic IED functions
Description
Ethernet link status
Frame rate is higher than normal state
Frame rate is higher than throttle state
Values (Range)
Unit
0=Off
-
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
%
-
-
-
-
-
-
-
-
-
-
-
-
Section 17
Description
Frame rate control state
Quota level in percent
0-100
Number of IP packets
received in normal mode
Number of IP packets
received in polled mode
Number of IP packets
discarded
Number of non IP
packets received in
normal mode
Number of non IP
packets received in
polled mode
Number of non IP
packets discarded