Signal outputs

Table 541:
Signal output and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC

Power outputs

Table 542:
Power output relays without TCS function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
Table 543:
Power output relays with TCS function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
Technical data
Value
250 V AC/DC
5 A
10 A
30 A
≤0.5 A/≤0.1 A/≤0.04 A
Value
250 V AC/DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
Value
250 V DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
20...250 V DC
~1.0 mA
20 V DC
Section 19
617