1MRK 504 135-UEN A
14.13.6
14.14
14.14.1
14.14.2
14.14.3
Technical manual
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase), (UBase) and (SBase).
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according
to
table
395.
Table 395:
Input integer value converted to binary output signals
Measured supervised
below low-low
value is:
limit
Output:
LOWLOW
High
LOW
NORMAL
HIGH
HIGHHIGH
Station battery supervision SPVNZBAT
Identification
Function description
Station battery supervision function
Function block
GUID-2D3C21EA-75E9-4E44-AA0F-4DEA7599182A V1 EN
Figure 211:
Function block
Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
between low‐
between low
low and low
and high limit
limit
High
High
IEC 61850
IEC 60617
identification
identification
SPVNZBAT
U<>
Section 14
Monitoring
between high-
above high-
high and high
high limit
limit
High
High
ANSI/IEEE C37.2
device number
-
489