1MRK 504 135-UEN A
12.2.6.2
Technical manual

Functionality

The interlocking for a double busbar double circuit breaker bay including
DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to a
double busbar arrangement according to figure 139.
QB1
QA1
DB_BUS_A
QB61
QB9
IEC04000518 V1 EN
Figure 139:
Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_BUS_A handles the circuit breaker QA1 that is connected to busbar WA1 and the
disconnectors and earthing switches of this section. DB_BUS_B handles the circuit
breaker QA2 that is connected to busbar WA2 and the disconnectors and earthing
switches of this section.
QB2
QC1
QA2
QC2
QB62
QC9
Section 12
Control
WA1 (A)
WA2 (B)
QC4
DB_BUS_B
QC5
QC3
DB_LINE
en04000518.vsd
303