Table 87:
EF4PTOC Group settings (basic)
Name
Values (Range)
Operation
EnaDir
AngleRCA
polMethod
UPolMin
IPolMin
RPol
XPol
I>Dir
2ndHarmStab
DirMode1
Table continues on next page
Technical manual
Name
ST2
ST3
ST4
STFW
STRV
2NDHARMD

Settings

Unit
Off
-
On
Disable
-
Enable
-180 - 180
Deg
Voltage
-
Current
Dual
1 - 100
%UB
2 - 100
%IB
0.50 - 1000.00
ohm
0.50 - 3000.00
ohm
1 - 100
%IB
5 - 100
%
Off
-
Non-directional
Forward
Reverse
Type
Description
BOOLEAN
Start signal step 2
BOOLEAN
Start signal step 3
BOOLEAN
Start signal step 4
BOOLEAN
Forward directional start signal
BOOLEAN
Reverse directional start signal
BOOLEAN
2nd harmonic block signal
Step
Default
-
Off
-
Enable
1
65
-
Voltage
1
1
1
5
0.01
5.00
0.01
40.00
1
10
1
20
-
Non-directional
Section 8
Current protection
Description
Operation Off / On
Enabling the Directional calculation
Relay characteristic angle (RCA)
Type of polarization
Minimum voltage level for polarization
(UN or U2) in % of UBase
Minimum current level for polarization (IN
or I2) in % of IBase
Real part of source Z to be used for
current polarisation
Imaginary part of source Z to be used for
current polarisation
Current level (IN or I2) for direction
release in % of IBase
Second harmonic restrain operation in %
of IN amplitude
Directional mode of step 1 (off, non-
directional, forward, reverse)
157