Section 14
Monitoring
14.12.2
14.12.3
14.12.4
14.12.5
Table 391:
MVGGIO Non group settings (basic)
Name
BasePrefix
MV db
MV zeroDb
MV hhLim
MV hLim
Table continues on next page
486

Functionality

IEC61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.

Function block

BLOCK
^IN

Signals

Table 389:
MVGGIO Input signals
Name
BLOCK
IN
Table 390:
MVGGIO Output signals
Name
VALUE
RANGE

Settings

Values (Range)
Unit
micro
-
milli
unit
kilo
Mega
Giga
Tera
1 - 300
Type
0 - 100000
m%
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
MVGGIO
^VALUE
RANGE
IEC09000239-2-en.vsd
Type
Default
Description
BOOLEAN
0
Block of function
REAL
0
Analog input value
Type
Description
REAL
Magnitude of deadband value
INTEGER
Range
Step
Default
-
unit
1
10
1
500
0.01
900.00
0.01
800.00
1MRK 504 135-UEN A
Description
Base prefix (multiplication factor)
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Zero point clamping in 0,001% of range
High High limit multiplied with the base
prefix (multiplication factor)
High limit multiplied with the base prefix
(multiplication factor)
Technical manual