Technical Data; Breaker Close/Trip Circuit Monitoring Tcsscbr; Identification; Functionality - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 11
Secondary system supervision
11.1.8
11.2
11.2.1
11.2.2
11.2.3
254

Technical data

Table 173:
SDDRFUF technical data
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change level
Operate current change level
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current

Breaker close/trip circuit monitoring TCSSCBR

Identification

Function description
Breaker close/trip circuit monitoring

Functionality

The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The trip circuit supervision generates a current of
approximately 1 mA through the supervised control circuit. The validity supervision
of a control circuit is provided for power output contacts T1, T2 and T3.
The trip circuit supervision operates after a settable definite operating time and resets
after a settable definite time when the fault disappears.

Function block

GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 115:
Function block
Range or value
(1-100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
1MRK 504 135-UEN A
Accuracy
± 1.0% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 5.0% of U
r
± 5.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
ANSI/IEEE C37.2
device number
-
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents