Settings; Monitored Data; Operation Principle - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 15
Metering
15.1.5
Table 433:
PCGGIO Non group settings (basic)
Name
Operation
EventMask
CountCriteria
Scale
Quantity
tReporting
15.1.6
15.1.7
526
Table 432:
PCGGIO Output signals
Name
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL

Settings

Values (Range)
Unit
Off
-
On
NoEvents
-
ReportEvents
Off
-
RisingEdge
Falling edge
OnChange
1.000 - 90000.000
-
Count
-
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
1 - 3600
s

Monitored data

Table 434:
PCGGIO Monitored data
Name
CNT_VAL
SCAL_VAL

Operation principle

The registration of pulses is done according to setting of CountCriteria parameter on
one of the 9 binary input channels located on the BIO module. Pulse counter values are
sent to the station HMI with predefined cyclicity without reset.
Type
Description
BOOLEAN
The pulse counter value is invalid
BOOLEAN
The reported value does not comprise a complete
integration cycle
BOOLEAN
The pulse counter function is blocked
BOOLEAN
A new pulse counter value is generated
REAL
Scaled value with time and status information
Step
Default
-
Off
-
NoEvents
-
RisingEdge
0.001
1.000
-
Count
1
60
Type
Values (Range)
INTEGER
-
REAL
-
1MRK 504 135-UEN A
Description
Operation Off/On
Report mask for analog events from pulse
counter
Pulse counter criteria
Scaling value for SCAL_VAL output to unit
per counted value
Measured quantity for SCAL_VAL output
Cycle time for reporting of counter value
Unit
Description
-
Actual pulse counter
value
-
Scaled value with time
and status information
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents