Section 16
Station communication
16.10
16.10.1
16.10.2
16.10.3
16.10.4
548
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the float values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive a single point value
GOOSESPRCV
Identification
Function description
GOOSE function block to receive a
single point value
Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
Function block
GOOSESPRCV
BLOCK
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 245:
GOOSESPRCV function block
Signals
Table 463:
GOOSESPRCV Input signals
Name
Type
BLOCK
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSESPRCV
-
Default
Description
0
Block of function
1MRK 504 135-UEN A
ANSI/IEEE C37.2
device number
-