1MRK 506 382-UEN A
17.4.10
17.4.10.1
Line distance protection REL650 2.2 IEC
Technical manual
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and communication
error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (in
case easy GOOSE engineering is enabled) to receive the measured
value.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.

GOOSE function block to receive a single point value

GOOSESPRCV

Identification

Function description
GOOSE function block to receive a
single point value
Station communication
Data Value
Data Valid
Updated
1
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Updated
1
Updated
1
Freeze
0
IEC 61850
IEC 60617
identification
identification
GOOSESPRCV
-
Section 17
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
ANSI/IEEE C37.2
device number
-
685