Settings; Operation Principle; Goose Function Block To Receive A Single Point Value Goosesprcv; Identification - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
14.7.5
Table 364:
GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Operation
14.7.6
14.8
14.8.1
Technical manual
Table 363:
GOOSEMVRCV Output signals
Name
MVOUT
DATAVALID
COMMVALID
TEST

Settings

Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the float values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive a single point value
GOOSESPRCV

Identification

Function description
GOOSE function block to receive a
single point value
Type
Description
REAL
Measurand value output
BOOLEAN
Data valid for measurand value output
BOOLEAN
Communication valid for measurand value output
BOOLEAN
Test output
Step
Default
-
Off
IEC 61850
identification
GOOSESPRCV
Section 14
Station communication
Description
Operation Off/On
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
447