Rapid Stop, Ramp-Up - Siemens SIMATIC EM 148-FC Manual

Frequency converter
Table of Contents

Advertisement

Rapid stop, ramp-up

Control bits
Bit 2
Bit 0
f
setpoint
Brake
Figure 5-6
The motor is stopped by means of a steeper ramp based on half the
parameterized ramp-down time.
The AUS3 command has a higher priority than AUS1. In other words, ramp down
triggered by AUS1 is continued by AUS3 as a rapid stop.
Caution
!
Frequent braking operations with high power consumption can heat up the motor
significantly, possibly resulting in excess temperature.
EM 148-FC Frequency Converter
A5E00065321-03
AUS3
1
0
1
0
f
f
max
0
Parameterized ramp-down
time
1
0
Rapid stop, ramp-up
Mode of Functioning
AUS1
t
t
5-7