Cu Analog Inputs Characteristic Value X1 / Cu Ai Char X1; Cu Analog Inputs Characteristic Value Y1 / Cu Ai Char Y1 - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Note
When changing p0756, the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten with
the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 1, p0757 is set to 2.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 6, 7, p0757 is set to 0 °C, p0758 = 0.0 %, p0759 = 100 °C and p0760 = 100.0 %.
X202: IO module terminal
p0757[0...3]

CU analog inputs characteristic value x1 / CU AI char x1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA, °C) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
p0758[0...3]

CU analog inputs characteristic value y1 / CU AI char y1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
160.000
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [%]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
0.000
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
0.00 [%]
569

Advertisement

Table of Contents
loading

Table of Contents