4.9.17.2
Connecting

Temperature sensor connections

Table 4- 51
X531-X536 temperature sensor inputs
Connector
Terminal
1
2
3
4
Max. connectable cross-section: #16 AWG (1.5 mm²)
Measuring current via temperature sensor connection: approx. 0.83 mA
When connecting temperature sensors with 3 wires, a jumper must be inserted between
X53x.2 and X53x.4.
Table 4- 52
Terminal
X531
X532
X533
X534
X535
X536
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Function
Function
1x2- / 2x2-wire
3- and 4-wire
+Temp
+
(channel x)
(Channel x)
-Temp
-
(channel x)
(Channel x)
+Temp
+ I
c
(channel y)
(constant current, posi-
tive channel x)
-Temp
- I
c
(channel y)
(constant current, nega-
tive channel x)
Channel assignment
Channel number [x]
for 1x2-, 3-, and 4-wires
0
1
2
3
4
5
4.9 Additional connections
Technical specifications
Temperature sensor connection for sensors with
1x2 wires
Connection of the 2nd measurement cable for
sensors with 4 wires
Temperature sensor connection for sensors with
1x2 wires
Connection of the 1st measurement cable for
sensors with 3 and 4 wires
Temperature sensor connection for sensors with
2x2, 3, and 4 wires
Channel number [y]
for 2x2-wires
6
7
8
9
10
11
Electrical installation
153