Fiber Management Installation (Optional); Power Connections - Alcatel-Lucent 1665 Installation Manual

Data multiplexer
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Physical installation
............................................................................................................................................................................................................................................................
Table 2-4 Power connections
Backplane
connection
P14
P15
Notes:
1. Power cables for shelves 4 and 2 are mounted using the connector mounting holes located
closest to the rear of the shelves with the cabling for shelf 2 bending away (out) from the
power connector in shelf 4 and running over it until the power cables exit the bay. The
power runs for shelves 1 and 3 are run in the same manner as described for shelves 2 and
4 using the connector holes located furthest from the rear of the shelf.

Fiber management installation (optional)

Description
This section describes how to install the fiber management pieces that may be shipped
with the bay.
Note:
extended by at least 2.5 inches beyond the bay upright on each side. This is typically
done using base fillers.
Comcode numbers are in parentheses next to the part.
Steps
........................................................................................................................................................................................................................
1
Locate three spools (106738156), one fiber radius control module (321-1B), one left fiber
spool bracket (848919213) and three M4 X 6 bracket mounting screws (901340059) for
each shelf being installed.
........................................................................................................................................................................................................................
2
For each spool, put a nylach fastener through the middle, then insert a pin halfway
through.
............................................................................................................................................................................................................................................................
2 - 2 0
Shelf power
connectors
(on sides)
Pin#
BAT A
1
2
BAT B
1
2
If fiber management is to be installed, the width of the bay footprint must be
Fiber management installation (optional)
Color
Designation
R
-48VA
W
-48RTNA
R
-48VB
W
-48RTNB
Name
BAT A
BAT A RTN
BAT B
BAT B RTN
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010