Installation tests
............................................................................................................................................................................................................................................................
Result:
MN and NE LEDs should be lit on the SYSCTL circuit pack.
........................................................................................................................................................................................................................
5
From the system view click Alarm List to verify that the circuit pack alarm is associated
with the optical port being tested.
........................................................................................................................................................................................................................
6
Select
Requirement: The flashing FAULT LED should extinguish on the OC-192 OLIU.
There should be no alarm indications on the Alcatel-Lucent 1665 DMX shelf.
........................................................................................................................................................................................................................
7
Remove the 15-dB LBO from the OC-192 OLIU.
........................................................................................................................................................................................................................
8
Replace all protective dust covers on the OC-192 OLIU connectors, that were removed to
perform this procedure.
........................................................................................................................................................................................................................
9
Repeat this entire procedure for each OC-192 OLIU in the Alcatel-Lucent 1665 DMX
shelf.
........................................................................................................................................................................................................................
10
Check off the appropriate box in
E
O
N D
........................................................................................................................................................
OC-192 facility loopback testing
Facility Loopback testing allows the installer to verify cabling to the OC-192 equipment.
This test is only required if the Alcatel-Lucent 1665 DMX shelf is connected to OC-192
equipment. If the shelf is NOT connected to OC-192 equipment, skip this section and
continue to the next chapter.
Note:
necessary for the testing.
The Function unit slot under test must contain an OC-192 (LNW603) circuit pack in order
to perform this test.
............................................................................................................................................................................................................................................................
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010
The FAULT LED should begin flashing on the OC-192 OLIU and only the
Configuration > Update System... > Update All
S
F
T E P S
An optical test set with the capability to transmit OC-192 SONET levels are
Table I-3, Installation acceptance
OC-192 (low-speed) testing
.
checklist.