Operational tests
........................................................................................................................................................................
A properly grounded ESD wrist strap must always be worn while handling circuit
packs.
This test should be performed on all shelves where office alarm reporting is required.
After completing the office alarm test, the Alcatel-Lucent 1665 DMX office alarms
should be disconnected from the office alarm system for the remainder of the test
procedures. This will prevent the office alarms from being activated while performing
the other tests in this section.
Table 7-1 Office alarm connections
Conn..
J12-J13
Office alarm test procedure
................................................................................................................................................
1
Connect the office alarm cable to J12 (ALM) on the backplane of the Alcatel-Lucent 1665
DMX shelf. If the shelf to be tested is part of a multiple shelf bay arrangement, the office
alarm cable connects to shelf 1.
................................................................................................................................................
2
Verify that one of the function groups is equipped with a pair of LNW7/LNW8/LNW801
DS1, LNW16/LNW19B DS3 or LNW18/LNW20 TMUX circuit packs.
................................................................................................................................................
3
Establish a CIT session by following the procedure under
software" (p. 5-6)
........................................................................................................................................................................
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010
Pin#
Color
Designation
1
BL-W
RYMJV1
2
W-BL
RYMJV2
3
O-W
RYMJA1
4
W-O
RYMJA2
5
G-W
RYMNV1
6
W-G
RYMNV2
7
BR-W
RYMNA1
8
W-BR
RYMNA2
9
S-W
RYCRV1
10
W-S
RYCRV2
11
BL-R
RYCRA1
12
R-BL
RYCRA2
in
Chapter 5, "Software download and circuit pack
Name
Minor Alarm Visible
Minor Alarm Visible Return
Minor Alarm Audible
Minor Alarm Audible Return
Major Alarm Visible
Major Alarm Visible Return
Major Alarm Audible
Major Alarm Audible Return
Critical Alarm Visible
Critical Alarm Visible Return
Critical Alarm Audible
Critical Alarm Audible Return
"Use of WaveStar
installation".
Office alarm test
®
CIT
7 - 3