Operational tests
........................................................................................................................................................................
................................................................................................................................................
12
Using a small flat bladed screwdriver, set one of the circuit breakers to OFF.
Result:
................................................................................................................................................
13
Press the ACO pushbutton on the SYSCTL.
Result:
The MJ audible alarm should clear.
................................................................................................................................................
14
Unseat the second circuit pack from the same function group pair as the circuit pack
removed in
Result:
................................................................................................................................................
15
Press the ACO pushbutton on the SYSCTL.
Result:
The CR audible alarm should clear.
................................................................................................................................................
16
Reseat the pair of function units.
................................................................................................................................................
17
Turn on the breaker that was turned off in
Result:
................................................................................................................................................
18
Disconnect the office alarm cable connected in
procedures in this chapter.
................................................................................................................................................
19
Select Configuration > Alarms > Alarm Severity Assignment Profile.
................................................................................................................................................
20
After screen appears, click the "+" next to ASAP Type System, Highlight DEFAULT and
click the Provision Button.
........................................................................................................................................................................
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010
Activated office alarms: MJ visual, MJ audible.
Activated office alarm: MJ visual.
Step
10.
Activated office alarms: CR visual, CR audible.
Activated office alarm: CR visual.
After a few minutes, all alarm indications should clear.