Connection Cross-Sections, Cable Lengths - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Table 4- 3
Dimensions of the cable lugs
Screw / bolts
Connection cross-section
M8
M10
M10
M12
M12
M12
M16
4.7.2

Connection cross-sections, cable lengths

Connection cross-sections
The connection cross-sections for the line connection, motor connection, and ground
connection for your device are specified in the tables provided in the "Technical
specifications" section.
Cable lengths
The maximum permissible cable lengths are specified for standard cable types or cable
types recommended by SIEMENS. Longer cables can only be used after consultation.
The listed cable length represents the actual distance between the converter and the motor,
taking account factors such as parallel laying, current-carrying capacity, and the laying
factor.
● Unshielded cable (e.g. Protodur NYY): max. 450 m
● Shielded cable (e.g., Protodur NYCWY, Protoflex EMV 3 Plus): max. 300 m.
Note
Cable lengths
The cable lengths specified are also valid if a motor reactor is in use.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
d2
[mm²]
[mm]
70
8.4
185
10.5
240
13
95
13
185
13
240
13
240
17
b
l
[mm]
[mm]
24
55
37
82
42
92
28
65
37
82
42
92
42
92
Electrical installation
4.7 Power connections
c1
c2
[mm]
[mm]
13
10
15
12
16
13
16
13
16
13
16
13
19
16
59

Advertisement

Table of Contents
loading

Table of Contents