Commissioning
5.3 Procedure for commissioning via STARTER
Configuring the drive unit
Figure 5-13
⇒ Under Connection voltage, choose the correct voltage. Under Cooling method: choose the
correct cooling method for your drive unit.
Note
Make a pre-selection
In this step, you make a preliminary selection of the chassis units. You do not define the line
voltage yet.
⇒ A list is now displayed under Drive unit selection:. Choose the corresponding drive unit
according to type (article no.) (see rating plate).
⇒ Click Continue >
138
Configuring the drive unit
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A