Siemens SINAMICS G130 Operating Instructions Manual page 140

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Commissioning
5.3 Procedure for commissioning via STARTER
NOTICE
Damage to the du/dt filter if it is not activated during commissioning
The du/dt filter may be damaged if it is not activated during commissioning.
• Activate the du/dt filter during commissioning by activating the appropriate checkbox
Note
Motor reactor
If a motor reactor (option CHK) is being used, the option selection must be activated,
otherwise the closed-loop motor control will not be able to operate in an optimum fashion.
Note
Check option selection
Carefully check the selected options against the options connected to your built-in unit.
Since the wizard establishes internal interconnections on the basis of the options selected,
you cannot change the selected options by clicking < Back.
If you make an incorrect entry, delete the entire drive unit from the project navigator and
create a new one.
⇒ Check your options carefully and then click Continue >
140
(option DU/DT).
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A