Technical data

7.4 Cable cross-sections and tightening torques

7.4
Cable cross-sections and tightening torques
Table 7-1
Connection, cross-section and tightening torque for PM240P-2 Power Modules
Inverters
Connection
FSD
Line supply,
motor
FSE
FSF
Line supply,
motor
62
Screw-type termi‐
10 ... 35 mm
nal
25 ... 70 mm
35 ... 2 × 120 mm
22 ... 25 Nm
Cable lug accord‐
ing to SN71322
Cross-section, tightening torque
Metric
, 2.5 ... 4.5 Nm
20 ... 10 AWG, 22 lbf in
2
8 ... 2 AWG, 40 lbf in
, 8 ... 10 Nm
6 ... 3/0 AWG, 88.5 lbf in
2
,
1 ... 2 × 4/0 AWG, 210 lbf in --
2
Hardware Installation Manual, 11/2016, A5E37800827C AB
Stripped
insulation
Imperial
length
18 mm
25 mm
PM240P-2 Power Modules