Examples of speed controller settings
A few examples of speed controller settings with vector control without encoders (p1300 =
20) are provided below. These should not be considered to be generally valid and must be
checked in terms of the control response required.
● Fans (large centrifugal masses) and pumps
Kp (p1470) = 2 ... 10
Tn (p1472) = 250 ... 500 ms
The Kp = 2 and Tn = 500 ms settings result in asymptotic approximation of the actual
speed to the setpoint speed after a setpoint step change. During many simple control
procedures, this is satisfactory for pumps and fans.
● Stone mills, separators (large centrifugal masses)
Kp (p1470) = 12 ... 20
Tn (p1472) = 500 ... 1000 ms
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Speed controller with/without encoder
CO: Speed setpoint after the filter
CO: Actual speed value smoothed
Automatic calculation of motor/control parameters
Rated motor startup time
Speed controller actual speed value smoothing time
Speed controller actual speed value smoothing time (without encoder)
Speed controller P gain adaptation speed lower
Speed controller integral time adaptation speed lower
Speed controller encoderless operation P gain
Speed controller encoderless operation integral time
CI: Speed controller torque setting value for motor holding brake
CI: Speed controller integrator setting value
CO: Speed controller I torque output
CO: Torque setpoint before supplementary torque
Rotating measurement selection
Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
349