Resonance damping

Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
The resonance damping is active in a range from approximately 6% of the rated motor
frequency (p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9
334
Voltage boost at startup active/inactive
Acceleration voltage active/inactive
Rated motor voltage
Rated motor current
Stator resistance, actual
Starting current (voltage boost) permanent
Starting current (voltage boost) when accelerating
Starting current (voltage boost) when starting
Voltage boost total