Setpoint channel and closed-loop control
7.3 V/f control
Parameter
• r0056.5
• r0056.6
• p0304
• p0305
• r0395
• p1310
• p1311
• p1312
• r1315
7.3.2
Resonance damping
Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
The resonance damping is active in a range from approximately 6% of the rated motor
frequency (p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9
334
Voltage boost at startup active/inactive
Acceleration voltage active/inactive
Rated motor voltage
Rated motor current
Stator resistance, actual
Starting current (voltage boost) permanent
Starting current (voltage boost) when accelerating
Starting current (voltage boost) when starting
Voltage boost total
Resonance damping
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A