Note
Possible plant standstill by withdrawing or inserting the memory card in operation
If the memory card is withdrawn or inserted during operation, then data can be lost, possibly
resulting in a plant standstill.
• Only withdraw and insert the memory card when the Control Unit is in a no-voltage
condition.
Note
Insertion direction for the memory card
Only insert the memory card as shown in the photo above (arrow at top right).
NOTICE
Memory card damage caused by electric fields or electrostatic discharge
Electrical fields or electrostatic discharge may result in the memory card being damaged
and so cause malfunctions.
• When removing and inserting the memory card, always observe the ESD regulations.
Note
Possible data loss when returning the Control Unit with memory card
When returning a defective Control Unit for repair or testing, the data on the memory card
(parameters, firmware, licenses, etc.) could be lost.
• Do not return the memory card as well, but rather keep it in a safe place so that it can be
inserted in the replacement unit.
Note
Please note that only SIEMENS memory cards can be used to operate the Control Unit.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Electrical installation
4.10 Signal connections
89