Siemens SINAMICS G130 Operating Instructions Manual page 351

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Figure 7-15
When correctly adapted, when accelerating, the speed controller only has to compensate
disturbance variables in its control loop. This is achieved with a relatively minor controlled
variable change at the controller output.
The effect of the pre-control variable can be adapted according to the application using the
weighting factor p1496. For p1496 = 100%, pre-control is calculated according to the motor
and load moment of inertia (p0341, p0342). A balancing filter is used automatically to
prevent the speed controller acting against the injected torque setpoint. The time constant of
the balancing filter corresponds to the equivalent delay time of the speed control loop. Speed
controller pre-control is correctly set (p1496 = 100%, calibration using p0342) if the I
component of the speed controller (r1482) does not change while ramping-up or ramping-
down in the range n > 20% x p0310. Thus, pre-control allows a new speed setpoint to be
approached without overshoot (prerequisite: torque limiting does switch in and the moment
of inertia remains constant).
If the speed controller is pre-controlled by means of injection, the speed setpoint (r0062) is
delayed with the same smoothing time (p1442 or p1452) as the actual value (r1445). This
ensures that no target/actual difference (r0064) occurs at the controller input during
acceleration, which would be attributable solely to the signal propagation time.
When speed pre-control is activated, the speed setpoint must be specified continuously or
without a higher interference level (avoids sudden torque changes). An appropriate signal
can be generated by smoothing the speed setpoint or activating ramp-function generator
rounding p1130 – p1131.
The startup time r0345 (T
and describes the time during which the unloaded drive can be accelerated with the rated
motor torque r0333 (M
r0345 = T
(60 x r0333)
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Speed controller with pre-control
) is a measure for the total moment of inertia J of the machine
startup
) from standstill to the rated motor speed p0311 (n
mot,rated
= J x (2 x π x n
startup
mot,rated
Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
) / (60 x M
) = p0341 x p0342 x (2 x π x p0311) /
mot,rated
).
mot,rated
351

Advertisement

Table of Contents
loading

Table of Contents