Siemens SINAMICS G130 Operating Instructions Manual page 500

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Diagnosis / faults and alarms
10.2 Diagnosis
Table 10- 2
Description of the LEDs on the CU320-2 PN Control Unit
LED
Color
RDY (READY)
---
Green
Red
Red/green
Orange
Green/
orange or
red/orange
COM
---
PROFIdrive
cyclic operation
Green
Red
OPT
---
(OPTION)
Green
Red
RDY and COM
Red
RDY and OPT
Orange
Any individual behaviors of the LED OPT are described at the respective Option Board.
1)
500
State
Description
OFF
The electronic power supply is missing or lies outside the permis-
sible tolerance range.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
0.5 Hz flashing light
Commissioning/reset
2 Hz flashing light
Writing to the memory card.
2 Hz flashing light
General fault
0.5 Hz flashing light
Control Unit is ready for operation.
However, there are no software licenses.
0.5 Hz flashing light
Firmware update in progress for the connected DRIVE-CLiQ com-
ponents.
2 Hz flashing light
Firmware update of components has been completed. Wait for
POWER ON of the respective component.
2 Hz flashing light
Component detection via LED is activated (p0124[0]).
Note:
Both options depend on the LED status when component recogni-
tion is activated via p0124[0] = 1.
OFF
Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when the Control Unit
is ready for operation (see LED RDY).
Continuous light
Cyclic communication is taking place.
0.5 Hz flashing light
Cyclic communication is still not completely running.
Possible causes:
- The controller is not transferring any setpoints.
- For isochronous operation, either none or a faulty Global Control
(GC) has been transferred from the controller.
- "Shared Device" has been selected and only one controller con-
nected.
0.5 Hz flashing light
Bus error, incorrect parameter assignment/configuration
2 Hz flashing light
Cyclic bus communication has been interrupted or could not be
established.
OFF
Electronic power supply missing or outside permissible tolerance
range.
The component is not ready for operation.
The Option Board is missing or an associated drive object has not
been created.
Continuous light
Option board is ready.
0.5 Hz flashing light
Depends on the option board used
Continuous light
Depends on the option board used
0.5 Hz flashing light
Depends on the option board used
2 Hz flashing light
This component has at least one fault.
The option board is not ready (e.g., after switching on).
2 Hz flashing light
Bus error - communication has been interrupted.
0.5 Hz flashing light
The firmware of the connected option board is being updated.
.
1)
.
1)
.
1)
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A

Advertisement

Table of Contents
loading

Table of Contents