Siemens SINAMICS G130 Operating Instructions Manual page 459

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Figure 9-17
Activation
The synchronized bypass without overlap (p1260 = 2) function can only be activated using a
control signal. It cannot be activated using a speed threshold.
Parameterization
Once the synchronized bypass without overlap (p1260 = 2) function has been activated, the
following parameters must be set.
Table 9- 8
Parameters
r1261.0
r1261.1
p1266 =
p1269[0] =
p1269[1] =
p3800 = 1
p3802 = r1261.2
p3809 =
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Example circuit for bypass with synchronizer without degree of overlapping
Parameter settings for bypass function with synchronizer without degree of overlapping
Signal "Command switch motor - power unit"
Signal "Command switch motor - line supply"
Control signal setting
Signal source for contactor K1 feedback
Signal source for contactor K2 feedback
Synchronization is activated
Synchronization activation is triggered by the bypass function
Setting the phase setpoint for synchronizing the drive to the line supply
Functions, monitoring, and protective functions
Description
9.3 Extended functions
459