General Specifications - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Technical specifications

12.2 General specifications

12.2
General specifications
Table 12- 1
General technical data
Electrical data
Line system configurations
Line frequency
Output frequency
Line power factor
total fundamental
factor
Converter efficiency
Short-circuit current rating
per IEC, in conjunction with
the specified fuses
Short-circuit current rating
per UL508C (up to 600 V), in
conjunction with the speci-
fied fuses
Switching at input
Overvoltage category
Mechanical data
Degree of protection
Class of protection
Cooling method
Sound pressure level L
pA
m)
Touch protection
Compliance with standards
Standards
CE mark
RI suppression
Approval
556
Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
47 ... 63 Hz
0 ... 300 Hz
≥ 0.96
0.75 ... 0.93
> 98%
1.1 ... 447 kW: 65 kA
448 ... 671 kW: 84 kA
672 ... 1193 kW: 170 kA
>1194 kW: 200 kA
1.1 ... 447 kW: 65 kA
448 ... 671 kW: 84 kA
672 ... 1193 kW: 170 kA
>1194 kW: 200 kA
Once every 3 minutes
III per EN 61800-5-1
IP20 (frame sizes FX and GX)

 I P00 (frame sizes HX and JX)
I per EN 61800-5-1
Forced air cooling AF according to EN 60146
(1
≤ 73 dB(A) at 50 Hz line frequency
≤ 75 dB(A) at 60 Hz line frequency
EN 50274 and BGV A3 when used as intended
EN 60146-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529
In accordance with EMC Directive No. 2014/30/EU and Low-Voltage Directive
No. 2014/35/EU and Machinery Directive No. 2006/42/EC
In accordance with the EMC product standard for variable-speed drives EN 61800-3, "sec-
ond environment".
Application in "first environment" possible with line filters
cULus (File No.: E192450) (only up to 600 V 3 AC)
.
1)
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A