Technical specifications
12.3 Technical specifications
Article number
Recommended fuses
- Line protection
without semiconductor protection
Rated current
frame size to IEC 60269
- Line and semiconductor protection
Rated current
Frame size to IEC 60269
Minimum short-circuit current
Rated output of a typ. 6-pole standard induction motor based on I
1)
Rated output of a typ. 6-pole standard induction motor based on I
2)
The base-load current I
3)
(see "Overload capability").
The base-load current I
4)
(see "Overload capability").
If the auxiliary supply is to be fed in separately from the load supply, e.g., if the control should be able to continue com-
5)
munication if the line voltage fails.
It is mandatory that the specified fuses are used to achieve a UL-approved system.
6)
The minimum current required to reliably trigger 3NE1 protective devices.
7)
570
6SL3310-
A
6)
A
A
7)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
1GF31-8AAx
1GF32-2AAx
3NA3244-6
3NA3252-6
250
315
2
2
3NE1227-2
3NE1230-2
250
315
1
1
2400
3000
or I
at 500 V 3 AC 50 Hz.
L
H
or I
at 575 V 3 AC 60 Hz.
L
H
Operating Instructions, 07/2016, A5E00331449A
1GF32-6AAx
3NA3354-6
355
3
3NE1331-2
350
2
3600
Inverter chassis units