Connection - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

4.10.5.2

Connection

X500: DRIVE-CLiQ interface
Table 4- 47
DRIVE-CLiQ interface X500
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
X524: Electronic power supply
Table 4- 48
Terminal block X524
Terminal
+
+
M
M
Max. connection cross-section: 2.5 mm²
The maximum cable length that can be connected is 10 m.
Note
Looping through the supply voltage
The two "+" and "M" terminals are jumpered in the connector and not in the unit.
This ensures that the supply voltage is looped through.
The power can be supplied via terminals X41:1/2 of the Power Module.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Function
Electronic power supply
Electronic power supply
Electronics ground
Electronics ground
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Technical data
Voltage: 24 VDC (20.4 to 28.8 V)
Current consumption: max. 0.55 A
Max. current via jumper in connector: 20 A (15 A
according to UL/CSA)
Electrical installation
4.10 Signal connections
117