Technical data

7.3 Cable cross-sections and tightening torques

Typical inverter load cycles
Image 7-1
7.3
Cable cross-sections and tightening torques
Table 7- 1
Connection type, cable cross sections and tightening torques
Inverters
Connection
FSA
Line, motor cable, DC
link and braking resistor
FSB
Line, motor cable, DC
link and braking resistor
FSC
Line, motor cable, DC
link and braking resistor
FSD
Line, motor cable, DC
link and braking resistor
FSE
Line, motor cable, DC
link and braking resistor
FSF
Line, motor cable, DC
link and braking resistor
FSGX
Line, motor cable, DC
link and braking resistor
The cross-section specifications refer to possible cable cross-sections for the terminals, not
the current that you require for your particular application.
64
"High Overload" and "Low Overload" load cycles
Terminal
1.0 ... 2.5 mm
Terminal
1.5 ... 6 mm
Terminal
4 ...10 mm: 2.3 Nm
Cable
10 ... 35 mm
lug
Cable
25 ... 50 mm
lug
Cable
35 ... 120 mm
lug
Cable
95 ... 2*240 mm
lug
Cross-section and tightening torque
Metric
1.1 Nm
18 ... 14 AWG: 9.7 lbf in
2
1.5 Nm
16 ... 10 AWG: 13 lbf in
2
12 ... 8 AWG: 20 lbf in
: 6 Nm
7 ... 2 AWG: 53 lbf in
2
: 6 Nm
3 ... 1 AWG: 53 lbf in
2
: 13 Nm
2 ... 4/0 AWG: 115 lbf in
2
: 14 Nm
3/0 ... 2*600 AWG: 120
2
lbf in
Hardware Installation Manual, 07/2016, A5E36985441C AA
Strip
lengths
Imperial
8 mm
8 mm
10 mm
--
--
--
--
Power Modules PM240