Parameter macros
Parameter macro p0015 = G130 built-in unit
This macro is used to make default settings for operating the built-in unit.
Table A- 1
Parameter macro p0015 = G130 built-in unit
Parameters
p0400[0]
Encoder type selection
p0404[0]
Encoder configuration
p0405[0]
Square-wave encoder track A/B
p0408[0]
Rotary encoder pulse No.
p0420[0]
Encoder connection
p0500
Technology application
p0600
Motor temperature sensor for moni-
toring
p0601
Motor temperature sensor type
p0603[0]
CI: Motor temperature
p0604
Motor overtemperature alarm
threshold
p0605
Motor overtemperature fault
threshold
p0606
Motor overtemperature timer
p0610
Response to motor overtempera-
ture condition
p0700[0]
Macro binector input (BI)
p0864
BI: Infeed operation
p1000[0]
Macro connector inputs (CI) for
speed setpoints
p1001
CO: Fixed speed setpoint 1
p1002
CO: Fixed speed setpoint 2
p1003
CO: Fixed speed setpoint 3
p1083
CO: Speed limit in positive direction
of rotation
p1086
CO: Speed limit in negative direc-
tion of rotation
p1115
Ramp-function generator selection
p1120
Ramp-function generator ramp-up
time
p1121
Ramp-function generator ramp-
down time
p1135
OFF3 ramp-down time
p1200
Flying restart operating mode
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Sink
Description
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
DO
Parameters
9999
User-defined
200008h
9h
Bipolar, like A/B track
1024
1024 pulses per revolution
0x2
Encoder connection = terminal
1
Pumps, fans
0
No sensor
0
No sensor
r4105
Sensor on TM31
120
120 °C
155
155 °C
0
0 s
12
Messages, no reduction of I_max,
temperature saved
70001
PROFIdrive
1
100001
PROFIdrive
300
300 rpm
600
600 rpm
1500
1500 rpm
6000
6000 rpm
-6000
-6000 rpm
1
Extended ramp-function genera-
tor
20
20 s
30
30 s
10
10 s
0
Flying restart not active
Appendix

A.2 Parameter macros

Source
Description
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
TM31
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
DO
591

Advertisement

Table of Contents
loading

Table of Contents