5.5.2
Basic commissioning
Entering the motor data
During initial commissioning, you have to enter motor data using the operator panel. Use the
data shown on the motor type plate.
Figure 5-41
Table 5- 1
Motor data
System of units for line frequency and entering motor data
Motor:
Rated voltage
Rated current
Rated power
Rated power factor cos ϕ (at p0100 = 0 only)
Rated efficiency η (at p0100 = 1only)
Rated frequency
Rated speed
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Example of a motor type plate
5.5 First commissioning with the AOP30
Parameter no.
Values
p0100
0
1
p0304
p0305
p0307
p0308
p0309
p0310
p0311
Commissioning
Unit
IEC [50 Hz / kW]
NEMA [60 Hz / hp]
[V]
[A]
[kW] / [hp]
[%]
[Hz]
[min-1] / [rpm]
173