Electrical installation
4.7 Power connections
4.7.4

DCPS, DCNS connection for a dV/dt filter with Voltage Peak Limiter

Table 4- 5
With frame sizes FX and GX, the connecting cables are routed down through the Power
Module and out.
4.7.5
Adjusting the fan voltage
The power supply for the device fan (1 AC 230 V) in the Power Module is generated from the
line supply using a transformer.
The transformer is fitted with primary taps so that it can be fine-tuned to the line voltage.
If necessary, the connection fitted in the factory, shown with a dashed line, must be
reconnected to the actual line voltage.
For the position of the setting terminals, see the "Connection overview" section.
Note
Number of transformers
One transformer is installed in frame sizes FX, GX and HX; two transformers are installed in
frame size JX. The two primary terminals on these devices must be set together.
Figure 4-8
The line voltage assignments for making the appropriate setting on the fan transformer are
indicated in the following tables.
62
DCPS, DCNS
Frame size
FX
GX
HX
JX
Setting terminals for the fan transformer (380 to 480 V 3 AC / 500 to 600 V 3 AC / 660 to
690 V 3 AC)
Connectable cross-section
1 x 70 mm²
1 x 70 mm²
1 x 185 mm²
2 x 185 mm²
Operating Instructions, 07/2016, A5E00331449A
Terminal screw
M8
M8
M10
M10