Siemens SINAMICS G130 Operating Instructions Manual page 179

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Note
Enter the motor-side filter
A filter on the motor side must be entered in p0230:
• Motor reactor: p0230 = 1
• du/dt filter compact plus Voltage Peak Limiter: p0230 = 2
• du/dt filter plus Voltage Peak Limiter p0230 = 2
• Siemens sine-wave filter: p0230 = 3
When p0230 = 4 "External sine-wave filter", a separate sine-wave filter can be entered. An
input mask for specific filter data then appears.
NOTICE
Damage to the sine-wave filter if it is not activated during commissioning
The sine-wave filter may be damaged if it is not activated during commissioning.
• Activate the sine-wave filter during commissioning.
NOTICE
Damage to the du/dt filter if it is not activated during commissioning
The du/dt filter may be damaged if it is not activated during commissioning.
• Activate the du/dt filter during commissioning.
Note
Motor reactor
If a motor reactor is being used, the option selection must be activated, otherwise the closed-
loop motor control will not be able to operate in an optimum fashion.
Note
Do not use a selection
The choice "no selection" is also available as default setting for the command and setpoint
sources; if selected, no default settings are applied for the command and setpoint sources.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
5.5 First commissioning with the AOP30
Commissioning
179