Diagnosis / faults and alarms

10.2 Diagnosis

10.2
Diagnosis
Description
This section describes procedures for identifying the causes of problems and the measures
you need to take to rectify them.
Note
Errors or malfunctions
If errors or malfunctions occur in the device, you must carefully check the possible causes
and take the necessary steps to rectify them. If you cannot identify the cause of the problem
or you discover that components are defective, your regional office or sales office should
contact Siemens Service and describe the problem in more detail. Addresses of contact
persons are listed in the preface.
10.2.1
Diagnostics via LEDs
Control Unit
Table 10- 1
Description of the LEDs on the CU320-2 DP Control Unit
LED
Color
RDY (READY)
---
Green
Red
Red/green
Orange
Green/
orange or
red/orange
498
State
Description
OFF
The electronic power supply is missing or lies outside the permis-
sible tolerance range.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
0.5 Hz flashing
Commissioning/reset
light
2 Hz flashing light
Writing to the memory card.
2 Hz flashing light
General fault
0.5 Hz flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz flashing
Firmware update in progress for the connected DRIVE-CLiQ com-
light
ponents.
2 Hz flashing light
Firmware update of components has been completed. Wait for
POWER ON of the respective component.
2 Hz flashing light
Component detection via LED is activated (p0124[0]).
Note:
Both options depend on the LED status when component recogni-
tion is activated via p0124[0] = 1.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A