Siemens SINAMICS G130 Operating Instructions Manual page 100

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Electrical installation
4.10 Signal connections
Note
Connection cables
The PROFINET interfaces support Auto MDI(X). It is therefore possible to use both
crossover and non-crossover cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are each equipped with a green and
a yellow LED. These LEDs indicate the following status information:
Table 4- 32
LED
Link port
Activity
port
T0, T1, T2: Measuring socket contacts
Table 4- 33
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, order number: 1893708
Note
Cable cross section
The measuring socket contacts are only suitable for cable cross-sections of 0.2 mm
1 mm
Note
Using the measuring socket contacts
The measuring socket contacts support commissioning and diagnostic functions. It must not
be connected for normal operation.
100
LED states on the X150 P1/P2 PROFINET interface
Color
State
-
Off
Green
Continuous
light
-
Off
Yellow
Flashing
light
Measuring socket contacts T0, T1, T2
Socket
M
T0
T1
T2
.
2
Description
Missing or faulty link
10 or 100 Mbit link available
No activity
Data is being received or sent at port x
Function
Ground
Measuring socket contact 0
Measuring socket contact 1
Measuring socket contact 2
Technical data
Voltage: 0... 5 V
Resolution: 8 bits
Load current: max. 3 mA
Continuous short-circuit proof
The reference potential is terminal M
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
to
2