Siemens SINAMICS G130 Operating Instructions Manual page 378

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.2 Drive functions
Table 9- 1
Data determined using p1910
Induction motor
p1910 = 1
p1910 = 3
Since the type plate data provides the initialization values for identification, you must ensure
that it is entered correctly and consistently (taking into account the connection type
(star/delta)) so that the above data can be determined.
It is advisable to enter the motor supply cable resistance (p0352) before the standstill
measurement (p1910) is performed, so that it can be subtracted from the total measured
resistance when the stator resistance is calculated (p0350).
Entering the cable resistance improves the accuracy of thermal resistance adaptation,
particularly when long supply cables are used. This governs behavior at low speeds,
particularly during encoderless vector control.
Figure 9-1
If an output filter (see p0230) or series inductance (p0353) is used, its data must also be
entered before the standstill measurement is carried out.
The inductance value is then subtracted from the total measured value of the leakage. With
sine-wave filters, only the stator resistance, valve threshold voltage, and valve interlocking
time are measured.
378
Stator resistance (p0350)
Rotor resistance (p0354)
Stator leakage inductance (p0356)
Rotor leakage inductance (p0358)
Magnetizing inductance (p0360)
Drive converter valve threshold voltage (p1825)
Converter valve interlocking times (p1828 ...
p1830)
Saturation characteristics (p0362 ... p0366)
Equivalent circuit diagram for induction motor and cable
Permanent-magnet synchronous motor
Stator resistance (p0350)
Stator resistance q axis (p0356)
Stator inductance d axis (p0357)
Drive converter valve threshold voltage
(p1825)
Converter valve interlocking times (p1828 ...
p1830)
not recommended
Notice: When encoder adjustment is complete,
the motor is automatically rotated approx. one
revolution in order to determine the zero marker
of the encoder.
Operating Instructions, 07/2016, A5E00331449A