X132: Digital inputs/outputs
Table 4- 16
Terminal block X132
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section: 1.5 mm²
DI: digital input; DI/DO: bidirectional digital input/output; M: Electronics ground; M2: reference potential
1)
The rapid inputs can be used as probe inputs or as inputs for the external zero mark
2)
Data for: V
= 24 V; load 48 Ω; high ("1") = 90% V
3)
cc
The maximum cable length that can be connected is 30 m.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Designation
1)
DI 4
Voltage (max.): -3 ... +30 VDC
Current consumption, typical: 9 mA at 24 V
DI 5
Electrical isolation: The reference potential is terminal M2
DI 6
Level (including ripple)
DI 7
High level: 15 ... 30 V
DI 20
Low-level: -3 ... +5 V
Input delay (typ.):
DI 21
For "0" → "1": 50 μs
For "1" → "0": 150 μs
M2
Reference potential for terminal 1 ... 6
M
Electronics ground
DI/DO 12
As input:
Voltage: -3 ... +30 VDC
DI/DO 13
Current consumption, typical: 9 mA at 24 V
M
Level (including ripple)
DI/DO 14
High level: 15 ... 30 V
DI/DO 15
Low-level: -3 ... +5 V
DI/DO 12, 13, 14, and 15 are "high-speed inputs"
M
Input delay (typ.):
For "0" → "1": 5 μs
For "1" → "0": 50 μs
As output:
Voltage: 24 V DC
Max. load current per output: 500 mA
Continuous short-circuit proof
Output delay (typ./max.):
For "0" → "1": 150 μs / 400 μs
For "1" → "0": 75 μs / 100 μs
Switching frequency:
For resistive load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: Max. 10 Hz
Maximum lamp load: 5 W
out
3)
; low ("0") = 10% V
out
Electrical installation
4.10 Signal connections
Technical data
2)
81