Siemens SINAMICS G130 Operating Instructions Manual page 329

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Table 7- 1
p1300 V/f characteristics
Parameter
Meaning
value
0
Linear characteristic
1
Linear characteristic
with flux current
control (FCC)
2
Parabolic character-
istic
3
Programmable char-
acteristic
4
Linear characteristic
and ECO
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Standard with variable voltage boost
Characteristic that compensates for voltage
losses in the stator resistance for static /
dynamic loads (flux current control FCC).
This is particularly useful for small motors,
since they have a relatively high stator re-
sistance.
Characteristic that takes into account the
motor torque curve (e.g. fan/pump).
Quadratic characteristic (f² characteristic)
Energy saving because the low voltage
also results in small currents and losses.
Characteristic that takes into account the
motor/machine torque characteristic.
Characteristic (see parameter value 0) and Eco mode at constant operating point.
At constant operating point, the efficiency is optimized by varying the voltage.
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
Setpoint channel and closed-loop control
Application / property
7.3 V/f control
329

Advertisement

Table of Contents
loading

Table of Contents