Table 5- 3
NOTICE
Material damage when selecting the incorrect encoder supply voltage
Once the encoder has been commissioned, the supply voltage (5/24 V) set for the encoder
is activated on the SMC30 module. The encoder may be damaged, if a 5 V encoder is
connected and the supply voltage has not been set correctly (bit 20 = "Yes," bit 21 = "No").
• Set the correct supply voltage for the connected encoder.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Meaning of the bit settings for p0405
Bit
Meaning
0
Signal
1
Level
2
Track monitoring
3
Zero pulse
4
Switching threshold
5
Pulse/direction
5.5 First commissioning with the AOP30
Value 0
Unipolar
HTL
None
24 V unipolar
Same as A/B track
Low
No
Commissioning
Value 1
Bipolar
TTL
A/B>< -A/B
High
Yes
177